  • Problem: A 90% efficient pump normally delivers 50GPM of 50 degree chilled water at a head of 20 feet of water with a rotational speed of 900 rpm.
  • Key step: What is the percent increase in break horsepower required to increase the volume flow rate by 10%.
  • Watch out: So we don't want to make the assumption that the pump is operating at maximum capacity.
  • Result: What I mean by that is BHP2 as compared to BHP1 is equal to the ratio of N2 to N1 cube.
  • ✅ Answer: C